| HOME > Circuit Breakers > General Electric > TP Frame |
PowerBreak (1600 Amp Frame)
TP Frame | ||||
Item Code: | TPVF5612B | |||
T | Frame Type | |||
P | Mounting | |||
VF | Trip Unit | |||
5 | Frame Rating | |||
6 | Volt | |||
12 | Sensor Rating | |||
B | Suffix | |||
Options: | ||||||
Frame Type | Mounting | Trip Unit | Frame Amp | Voltage | Sensor Amp | Suffix |
T=Standard | P=Stationary | MM=MagneTrip | 3=800A | 6=600Vac/250Vdc | 02=200A | A2/T1=Targets-Overload,Short Circuit |
TH=Hi-Break | C=Draw-Out | R=MicroVersa Trip PM or Plus | 5=1600A | 7=750Vac/700Vdc | 04=400A | A3/T2=Targets-Overload,Short Circuit, Ground Fault |
TU=Special Hi-Break | S=MicroVersa Trip RMS-9 | 6=2000A | 06=600A | B=Inverted Construction | ||
SS=MicroVersa Trip RMS-9 | 7=2500A | 08=800A | E1=120VAC Electrical Motor Operation | |||
V=MicroVersa Trip | 8=3000A | 10=1000A | E2=240VAC Electrical Motor Operation | |||
VF=MicroVersa Trip | 9=4000A | 12=1200A | E3=125VDC Electrical Motor Operation | |||
VVF=MicroVersa Trip | 16=1600A | E5=24VDC Electrical Motor Operation | ||||
YY=Molded Case Switch | 20=2000A | E6=48VDC Electrical Motor Operation | ||||
25=2500A | E7=72VDC Electrical Motor Operation | |||||
30=3000A | FC=Front Connected(Stationary Only) | |||||
40=4000A | G=Ground Fault Trip Protection | |||||
G1=Adjustable Ground Fault 3 Phase 4 Wire | ||||||
G3=Adjustable Ground Fault 3 Phase 3 Wire | ||||||
H=High Range Instantaneous | ||||||
I=Instantaneous Trip Protection | ||||||
K=Kirk Key | ||||||
L=Long-Time Trip Protection | ||||||
S=Short-Time Trip Protection | ||||||
M=Metering/Communications | ||||||
P=Protective Relays/Communication | ||||||
Z1=GF Zone Selective Interlock | ||||||
Z2=GF/ST Zone Selective Interlock |
Interrupting Capacity Rating | ||||||
Frame | Voltage | 800 Amp | 1600 Amp | 2000 Amp | 3000 Amp | 4000 Amp |
Standard Break | 240 Vac | 65kAIC | 85kAIC | 85kAIC | 100kAIC | 100kAIC |
Standard Break | 480 Vac | 65kAIC | 65kAIC | 65kAIC | 100kAIC | 100kAIC |
Standard Break | 600 Vac | 42kAIC | 50kAIC | 50kAIC | 85kAIC | 85kAIC |
Standard Break | 250 Vdc | - | 22kAIC | - | 42kAIC | 42kAIC |
High Break | 240 Vac | 100kAIC | 125kAIC | 125kAIC | 200kAIC | 200kAIC |
High Break | 480 Vac | 100kAIC | 100kAIC | 100kAIC | 150kAIC | 150kAIC |
High Break | 600 Vac | 65kAIC | 65kAIC | 65kAIC | 100kAIC | 100kAIC |
High Break | 250 Vdc | - | 35kAIC | - | 85kAIC | 85kAIC |
High Break | 500 Vdc | - | - | - | 65kAIC | 65kAIC |
High Break | 600 Vdc | - | - | - | 65kAIC | 65kAIC |
Special High Break | 750 Vac | - | - | - | 35kAIC | 35kAIC |
Special High Break | 700 Vac | - | - | - | 65kAIC | 65kAIC |